Skip to content
Trafo Power and Electricals Pvt. Ltd.

Distribution

Distribution Transformers

Low-loss, BIS-marked distribution transformers for utilities, industry and infrastructure.

25 kVA – 3,150 kVA · up to 33 kV

Distribution transformer

Data sheet

Technical data

Technical data for Distribution Transformers
Rating25 kVA – 3,150 kVA
Voltage classup to 33 kV
Rating
Capacity25 kVA – 3,150 kVA
Voltage class0.433 / 11 / 22 / 33 kV
Construction
CoreCRGO / amorphous as per customer requirement
TypeHermetically sealed (gas cushion / fully filled) or conventional with conservator
Protection
CSPCompletely Self-Protected feature up to 400 kVA
Regulation
Tap changerOLTC with RTCC & AVR above 500 kVA, if required
Cooling
CoolingONAN / ONAF with corrugation or pressed-steel radiators
Compliance
BISBIS-marked conforming to IS 1180 (Part 1): 2014
Standards
Designed toIS 1180 (Part 1): 2014, IS 2026, IEC 60076, ANSI, BS

Final ratings, losses, impedance and dimensions are confirmed in the guaranteed technical particulars (GTP) for each order.

Overview

Three-phase oil-immersed distribution transformers, hermetically sealed or conventional, with CRGO or amorphous cores and optional CSP protection.

Distribution transformers can be free-breathing or hermetically sealed. Conventional units carry a conservator with breather; hermetically sealed units have a bolted cover with a gas cushion or are fully filled. Trafo Power's transformers are BIS-marked conforming to IS 1180 (Part 1): 2014, and designs are generally built to IEC 60076 and IS 2026.

Applications

  • Utility distribution networks
  • Industrial and commercial supply
  • Infrastructure and real estate
  • Power supply to facilities outside settlements

Design & engineering features

  • CRGO or amorphous core, per requirement
  • Hermetically sealed (gas cushion / fully filled) or conventional with conservator
  • Completely Self-Protected (CSP) option up to 400 kVA
  • OLTC with RTCC & AVR above 500 kVA, if required
  • ONAN / ONAF cooling with corrugated fins or pressed-steel radiators
  • Indoor or outdoor; colour and safety devices to specification
Rows of distribution transformers with bushings and conservators
Photograph · Trafo Power

Enquire

Request a quotation for distribution transformers

Share what you know — rating, voltages, standards, site and timeline. Our engineers will follow up with a GTP and guaranteed losses.